Do you need some help?

Call us now on: 01706 242050

1SFL647001R6811 af1250-30-11 24-60v -dc ABB Contactor

SKU
AF1250-30-11 24-60V

Contact us for pricing and availability.
Call us now on 01706 242050

1SFL647001R6811

Dimensions
Product Net Width: 210.0 mm
Product Net Depth: 242.0 mm
Product Net Height: 344.0 mm
Product Net Weight: 15.000 kg

Technical
Number of Main Contacts NO: 3
Number of Main Contacts NC: 0
Number of Auxiliary Contacts NO: 1
Number of Auxiliary Contacts NC: 1
Rated Operational Voltage: Main Circuit 1000 V
Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 1050 A
Rated Operational Current AC-1 (Ie):
(690 V) 55 °C 1040 A
(690 V) 40 °C 1260 A
(1000 V) 40 °C 1260 A
(1000 V) 55 °C 1040 A
(690 V) 70 °C 875 A
(1000 V) 70 °C 875 A
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: 8 x Ie AC-3
Rated Making Capacity AC-3 acc. to IEC 60947-4-1: 10 x Ie AC-3
Rated Short-time Withstand Current (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 8000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 7200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 5200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 4000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1500 A
Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 7500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 7000 A
Maximum Electrical Switching Frequency: AC-1 300 cycles per hour
Rated Operational Current DC-1 (Ie):
(850 V) 3 Poles in Series, 40 °C 1250 A
(600 V) 3 Poles in Series, 40 °C 1250 A
(220 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-3 (Ie):
(850 V) 3 Poles in Series, 40 °C 1250 A
(600 V) 3 Poles in Series, 40 °C 1250 A
(220 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-5 (Ie):
(850 V) 3 Poles in Series, 40 °C 1250 A
(600 V) 3 Poles in Series, 40 °C 1250 A
(220 V) 3 Poles in Series, 40 °C 1250 A
Rated Insulation Voltage (Ui):
acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Impulse Withstand Voltage (Uimp): Main Circuit 8 kV
Mechanical Durability: 0.5 million
Maximum Mechanical Switching Frequency: 300 cycles per hour
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C
Rated Control Circuit Voltage (Uc): DC Operation 20 … 60 V
Coil Consumption:
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 780 V·A
Holding at Max. Rated Control Circuit Voltage DC 5.5 V·A
Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 785 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 780 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A
Operate Time:
Between Coil Energization and NO Contact Closing 50 … 120 ms
Between Coil De-energization and NO Contact Opening 53 … 73 ms
Between Coil De-energization and NC Contact Closing 50 … 70 ms
Between Coil Energization and NC Contact Opening 45 … 115 ms
Connecting Capacity Main Circuit: Bar 50 mm
Connecting Capacity Auxiliary Circuit:
Solid 2x1…4 mm²
Flexible with Insulated Ferrule 1x0.75…2.5 mm²
Stranded 2x1…4 mm²
Flexible 1x0.75…2.5 mm²
Flexible with Ferrule 2x0.75…2.5 mm²
Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Connecting terminals (delivered in open position) Main poles: M 3.5 (+,-) pozidriv 2 screw with cable clamp
Terminal Type: Main Circuit: Bars

More Information
Depth 143mm
Manufacturer ABB
Alternative Product SKU 1SFL647001R6811
Manufacturer Part Number AF1250-30-11 24-60V
Packed Quantity 1
Inbuilt Aux 1 N/O, 1 N/C
Product Lead Time Please contact us for a delivery time
Links Click here for link to ABB website info (opens in new tab)
Write Your Own Review
You're reviewing:1SFL647001R6811 af1250-30-11 24-60v -dc ABB Contactor

ABB AF Contactor Range

ABB contactor range can be used to control power circuits up to a level of 690 V AC and 220 V DC. The main benefit of ABB's range of AF products are that only a few coils are needed for different control voltages used in many applications without having to change the coil.

These four coil voltages run from between 24...500 V 50/60 Hz or 20...500 V DC. These are AC/DC dual rated which cover a range of amperages rather than set specifications. ABB's AF contactors have built in surge protection and do not require any other surge suppressors.

Accessories are available in the form of front and side mounted auxiliary contact blocks plus being designed as a 1 stack 3 pole block type contactor they can have a one main auxiliary contact. Replacement parts are available as well as other accessories.

You can click on this link to view more ABB information

Latest News

Our top tips for maintaining your Variable Speed Drives

Our top tips for maintaining your Variable Speed Drives

October 15, 2024 Read full
We're a trusted distributor for IMO - a true British success story

We're a trusted distributor for IMO - a true British success story

September 26, 2024 Read full
Why are WAGO controllers so popular with UK operations managers?

Why are WAGO controllers so popular with UK operations managers?

September 24, 2024 Read full
A truly “brilliant” solution – introducing the Finder 7L Series!

A truly “brilliant” solution – introducing the Finder 7L Series!

August 30, 2024 Read full